The Switching Surge Defined
The switching surge comes in many different forms, and has many different sources. What is consistent between all switching surge events are:
- They are low frequency events usually under a kilohertz and related to the fundamental power frequency.
- They are always associated with a change in the operating state of the system.
- They are always associated with a switching event on the power system.
- They always involve trapped energy and its release.
Unlike the lightning surge, the switching surge is generally self induced by the operation of a breaker, switch or disconnect switch. However switching surges can be associated with lightning if during a lightning storm a lightning surge causes a breaker to operate and a switching surge is induced.
Figure 1 is an example of a typical switching surge. The wave shape is very complex. The amplitude of this switching surge is about 2.5 pu which is a quite common amplitude for switching surges. Also note the duration of this event is not much more than one power frequency cycle which again is quite common in switching surge events.
Sources of Switching Surges


Another scenario is if upon closing or opening S2 and S3 either pre-strikes or re-strikes of the switch can lead to switching surges 2pu to 3pu as shown in Figure 3.